Air-gapped and high-security network architectures: isolation, data diodes and controlled transfers
In short: Some networks are too sensitive to connect to the internet or even to the rest of the organisation. A true air gap has no network connection at all; data moves on controlled media or through one-way data diodes. Isolation brings real challenges, such as patching, time, monitoring and convenience pressure, and history shows attackers target the transfer points, so every path in and out must be controlled and logged.
Where air gaps are used
- Classified government and defence networks.
- Critical industrial control systems: power generation, water, chemical plants (often with tightly controlled one-way connections rather than full air gaps).
- Payment and banking core systems in some designs.
- Research labs, election systems and backup "vaults" designed to survive ransomware.
Degrees of isolation
- True air gap: no network connection to any other network, physically separate equipment, cabling and often rooms.
- One-way connection: a data diode (unidirectional gateway) physically allows data to flow in only one direction, for example sending OT data out to a monitoring network without any path back in.
- Cross-domain solutions: specialised, accredited gateways that inspect and filter data moving between networks of different classification.
- Logical isolation: firewalls and VRFs only. Useful, but not an air gap.
The transfer problem
Even isolated networks need data: software updates, antivirus signatures, files, configuration. Each transfer is a risk. Stuxnet, discovered in 2010, reached isolated industrial systems most likely through infected USB drives. Controls include:
- dedicated, scanned transfer stations ("kiosks") with several malware engines;
- approved, encrypted, numbered media only, with USB ports otherwise disabled;
- two-person rules and a transfer log;
- data diodes for regular one-way feeds.
Running an isolated network
- Updates: offline patch repositories (for example an offline WSUS or local Linux mirrors) refreshed through the controlled transfer process, tested before release.
- Time: local NTP servers with GPS or other GNSS receivers, since internet time is not available.
- Monitoring: a local SIEM and logging inside the enclave, or one-way export of logs through a diode.
- Identity: a separate directory, not trusted by or trusting the corporate one.
- Physical security: access control to rooms and equipment, tamper seals, and checks for unauthorised wireless devices.
Common failures
- "Temporary" network connections for vendor support that are never removed.
- Dual-homed laptops or engineering workstations bridging both networks.
- Wireless or cellular modems hidden in equipment.
- Pressure to make things convenient, slowly eroding the isolation.
Real-world example: the vendor's modem
A water utility believed its treatment plant control network was air-gapped. An audit found a cellular modem installed years earlier by an equipment vendor for remote support, with a default password, connected directly to the control network. It was removed, and vendor access was moved to a supervised, time-limited remote access service through a one-way monitored gateway.
Practice
What does a data diode do?
Why are transfer points the main risk for air-gapped networks?
How do isolated networks get accurate time without the internet?
Key takeaways
- Air gaps protect the most sensitive systems by removing network connections.
- Data diodes and cross-domain solutions provide controlled, one-way or filtered transfer.
- Control and log every transfer; disable unapproved media.
- Plan offline updates, local time and monitoring, and guard against hidden connections.
Original content written by Mohamed Fayas for FM TecHub. © 2026 FM TecHub. You're welcome to share a link to this page; please don't copy the text elsewhere without permission.