In short: Structured cabling runs permanent cables from a comms room patch panel to wall or floor outlets, with short patch leads at each end. Keep the permanent run within 90 metres, choose Cat6A for new installations, use one wiring standard throughout, label every panel port and outlet, keep racks tidy, and certify every run after installation.

Why "structured"

In a messy installation, long cables run straight from switches to desks, nobody knows which cable goes where, and every move means pulling new cable. Structured cabling separates the permanent part, installed once in walls and ceilings, from the patching part, which you change as people and devices move.

A structured cabling runSwitch portin the rackPatch leadshort,replaceablePatch panellabelledportHorizontalcableup to 90 m,fixedWall outletlabelledDevice leadto the PC
Figure 1. Permanent cables run between labelled panels and outlets; only short patch leads ever move.

The 100 metre channel

Twisted-pair Ethernet is specified for a channel of up to 100 metres: up to 90 metres of solid horizontal cable from panel to outlet, plus up to 10 metres of stranded patch leads in total at both ends. Longer runs need a switch closer to the users or fibre.

Cable categories

CategoryTypical use
Cat5e1 Gbps up to 100 m; 2.5 Gbps usually works
Cat61 Gbps; 10 Gbps up to about 55 m; 5 Gbps generally fine
Cat6A10 Gbps to 100 m; best choice for new installations and Wi-Fi 6E/7 APs
Cat825/40 Gbps up to 30 m, mainly in data centres

Use solid-core cable for permanent runs and stranded for patch leads. In many countries, fire regulations require low-smoke (LSZH) or plenum-rated cable in certain spaces.

T568A or T568B

These are two colour orders for wiring RJ45 plugs and jacks. Both work equally well; the important rule is to use one standard everywhere in a building. A patch lead wired the same at both ends is "straight-through"; with A at one end and B at the other it is a crossover, which modern ports no longer need because of auto-MDIX.

Labelling

Every panel port and its outlet should share a unique label, for example 2B-14 meaning floor 2, panel B, port 14, printed on both the panel and the wall plate. Record it in your documentation or IPAM tool with the switch port it is patched to. Labels save hours every time someone asks "which port is desk 2.14?".

Rack tidiness

  • Alternate patch panels and switches so patch leads are short (0.3 to 1 m).
  • Use horizontal and vertical cable managers; colour-code leads (for example blue data, yellow voice, red uplinks).
  • Leave space for airflow; keep power cables apart from data cables.
  • Do not over-tighten cable ties on Cat6A; use hook-and-loop strips.

Testing and certification

A simple tester checks that the eight wires are connected in the right order. A certification tester measures loss, crosstalk and length against the category standard and produces a report for each run. Ask installers for certification reports; most cable manufacturers require them for their 15 to 25 year warranty.

Real-world example: the 10 Gbps access points that ran at 1 Gbps

A school installed Wi-Fi 6E access points with 5 Gbps ports, but most negotiated only 1 Gbps. The building used old Cat5e cable, some of it over 100 m including patch leads, with untwisted ends at the jacks. Re-terminating the shorter runs restored 2.5 Gbps, and the longest runs were replaced with Cat6A as part of the summer works.

Practice

What is the maximum length of the permanent horizontal cable in a twisted-pair channel?
90 metres (100 metres for the full channel including patch leads).
Which cable category is recommended for new installations needing 10 Gbps to 100 m?
Cat6A.
Is T568A or T568B better?
Neither; both work. The rule is to use the same standard throughout the installation.

Key takeaways

  • Separate permanent cabling from patch leads.
  • Keep the channel within 100 m: 90 m fixed plus 10 m of patch leads.
  • Choose Cat6A for new work, one wiring standard and clear labels everywhere.
  • Keep racks tidy and get certification reports for every run.
Tracks your learning on this device only. See your progress on the learning paths.
Verified author✓ Valid
Issued to
Mohamed Fayas
Role
Founder of FM TecHub
Credentials
CCNABTEC HND Network EngineeringBEng (Hons) Computer Networking & Cloud Security
Issuer
FM TecHub · fmtechub.com

He writes practical, plain-English guides on networking, security and cloud.

More about the author →

Original content written by Mohamed Fayas for FM TecHub. © 2026 FM TecHub. You're welcome to share a link to this page; please don't copy the text elsewhere without permission.

Email updates: coming soon

New notes, tools and security news from FM TecHub by email, explained simply. Free. We're not collecting email addresses yet; see our privacy policy.

PortServiceStatus
SMTP/25Email updatesopening soon

Meanwhile, stay connected: